A hot water storage tank is a pressurised, sealed vessel. A sensor that screws straight into the water means isolating the tank, draining it, breaking a gasket and refilling — for what is often a five-minute component swap. This probe is made for the alternative: it slides into the tank's dry sensor pocket, a closed metal well welded into the shell. An NTC 10K B3950 element in a Ø6 × 50 mm stainless probe, epoxy-sealed, on 3 m of PVC two-core cable. The water never touches the sensor, the vessel stays sealed, and the probe pulls straight out when it needs testing or replacing.
In one line — a dry-pocket NTC 10K B3950 tank temperature probe that feeds stored-water temperature back to a gas boiler controller or thermostat, for hot water storage tanks, DHW cylinders and boiler-linked thermal stores.
Every direct-immersion fitting is another penetration in a pressurised, insulated cylinder. Removing one means isolation, drain-down, a new gasket and a leak test — and on a certified unvented unit, it can void the approval.
The pocket is welded once; the probe never enters the water pathTemperature probes are consumables compared with the tank. If a service engineer has to drain 200 litres to check a thermistor, the call-out becomes a half-day job and the customer pays for it twice.
Pull the probe out, test it, slide a new one in — system stays full and liveA tank in a boiler room sits next to flues, flow pipes and unlagged fittings. A PVC lead dressed against a hot surface hardens, cracks and eventually reads the wrong resistance.
Route the lead away from heat; keep the cable environment ≤80 °C
Be clear about the trade-off. A dry pocket adds an air gap between the water and the element, so the reading responds more slowly and sits slightly below the true water temperature compared with a wetted probe. For boiler control — where the tank changes temperature over tens of minutes, not seconds — that is a good trade. Section 8 explains how to keep the error small, and why the pocket fit matters more than the thermistor.
The resistance curve most gas boiler and DHW controller inputs are built for. A 10K element gives a strong signal over a 3 m lead without the lead resistance dominating the measurement.
The beta value defines the shape of the curve away from 25 °C. Two 10K probes with different beta values agree at room temperature and disagree at 60 °C — see Section 9 before ordering.
A tight part-to-part spread means one probe can be swapped for another without recalibrating the controller. It is a resistance tolerance at 25 °C — not a ±1 % or ±1 °C temperature accuracy claim.
A slim, long body that reaches the bottom of a standard dry pocket and stays in full contact with the well. Stainless resists the condensate and scale found around tank fittings.
The element is potted inside the probe, so vibration during transport and the humidity of a boiler room cannot shift the bead or let moisture track down the cable into the sensing end.
Enough lead to reach the boiler terminal strip from a tank mounted alongside it. A 30 mm stripped tail with 3 mm tinned ends lands directly in a screw terminal — no ferrules, no plug to source.
The NTC bead sits close to the closed tip inside the Ø6 mm shell, potted in epoxy. That puts the sensing point where the pocket is hottest, holds the bead against vibration and seals the cable entry against moisture ingress.
Red and black cores, 24 AWG, 3 m long. PVC is flexible and easy to dress through a boiler room — but it is a ≤80 °C routing material, not a high-temperature lead. Keep it off flues, flow pipes and the tank shell.
Long enough to land both cores in a terminal block with a service loop left inside the boiler enclosure. A 3 mm tinned tip takes a screw clamp cleanly without stray strands shorting the adjacent terminal.
An NTC is a pure resistance, so the two cores can be landed either way round. No connector is supplied as standard — the probe terminates at the controller you already have, which keeps one part compatible with many boiler brands.
Confirm the pocket bore matches the Ø6 mm probe, is dry and free of scale or debris, and is deep enough for the full 50 mm. An oversized or fouled well leaves an air gap that dominates the error.
Slide it all the way to the bottom of the well and secure the lead so it cannot work loose. A probe that stops 20 mm short sits in cooler air and reads low — the single most common installation fault.
Dress the 3 m lead clear of flues, unlagged flow pipework and the tank shell. Keep the cable route environment at ≤80 °C, leave a small service loop at the probe, and clip the cable so no weight hangs on the terminals.
Land the two cores on the NTC 10K / B3950 sensor input of the boiler controller or thermostat. NTC has no polarity. Compare the displayed value with a reference thermometer at a known tank temperature before handover.
The standard arrangement in the illustration: a wall-hung gas boiler heats an indirect cylinder, and the controller uses the tank probe to decide when to call for heat and when to satisfy the setpoint.
Domestic hot water cylinders where the manufacturer provides a dry pocket as standard. Fitting into the existing well keeps the vessel certification and the pressure boundary untouched.
Buffer vessels on heat pump, solar-thermal and boiler hybrid systems, where upper-pocket temperature drives the boiler enable signal and a second point may be used for stratification monitoring.
Replacing a failed OEM probe on an installed cylinder without drain-down. Send the pocket bore and depth and the controller curve — we will match the probe length and termination to the existing well.
Report the temperature at the sensor pocket as an NTC resistance signal; give the boiler controller the stored-water feedback it needs to start and stop a heat call; support straightforward service replacement.
Act as a certified high-limit thermostat or overheat cut-out; provide Legionella or scald protection; replace the boiler's own safety sensors, flue thermostat or pressure devices; make autonomous control decisions.
For safety-critical functions — overheat cut-out, unvented cylinder high-limit, scald protection — use devices qualified to the relevant standard and follow the cylinder and boiler manufacturers' protection design. We are glad to supply the sensing point around that system, but we will not represent this probe as a safety device.
This is the most commonly misread line on the specification sheet. The published ±1 % describes the spread of the element's resistance at 25 °C (R25) from one probe to the next. It is not ±1 % of reading across the range, and it is certainly not ±1 °C at 60 °C. As the specification graphic itself states: final system accuracy depends on controller, installation and calibration.
| What determines the final reading | What it contributes |
|---|---|
| NTC R25 tolerance (±1 %) | Part-to-part spread; roughly a fraction of a degree near 25 °C |
| Beta value / curve match in the controller | Several degrees of error away from 25 °C if the curve is wrong |
| Controller input linearity & ADC | Controller-dependent; check the manufacturer's specification |
| Dry-pocket fit, depth and air gap | Usually the largest installation contribution |
| Cable routing temperature | Lead resistance drift if the PVC jacket is overheated |
| Calibration / offset in the controller | Used to trim the installed loop at a known temperature |
We do not publish a system accuracy figure for this probe, because we do not supply the controller or install the pocket. Any stated system accuracy must come from the completed, commissioned loop.
| Installation condition | Typical effect on the reading |
|---|---|
| Probe fully seated in a clean, correctly sized dry pocket | Close to water temperature; slower response than a wetted probe |
| Probe only part-inserted, or an oversized pocket with a wide air gap | Reads low, lags noticeably behind tank changes |
| Scale, debris or moisture inside the pocket | Unreliable and slow — clean the well before fitting |
| Pocket in a strongly stratified tank | Reads that layer only, not the tank average (see Section 6) |
| Cable dressed against a flue or hot flow pipe | Lead resistance drift, intermittent or implausible values |
| Controller configured for a different beta value | Plausible but wrong temperature, with no fault raised |
Indicative behaviour for steady-state boiler control. For a certified or safety-related temperature value, use a qualified device and a calibrated control loop.
"10 kΩ" describes the resistance at 25 °C only. Two 10K NTCs with different beta values read the same at room temperature and diverge by several degrees at 60 °C. The controller input curve must match the probe.
| Curve | R at 25 °C | Beta | Typical use |
|---|---|---|---|
| NTC 10K B3950 | 10 kΩ | 3950 K | This sensor — gas boiler / DHW controller inputs |
| NTC 10K B3977 / B3435 | 10 kΩ | 3977 / 3435 K | Brand-specific boiler and HVAC controls |
| NTC 100K B3950 | 100 kΩ | 3950 K | Some BMS and cabinet controllers |
| PT1000 / Pt100 | ≈ 1097 / 109.7 Ω | — | RTD inputs; resistance rises with temperature, not interchangeable |
Wiring is simple, but not optional. An NTC has no polarity, so the red and black cores can be landed either way round on the sensor input. Keep both cores on the same input pair, away from mains terminals, and verify the displayed reading against a reference thermometer at a known tank temperature during commissioning.
| Sensor element | NTC thermistor, 10 kΩ at 25 °C |
| Beta value (B25/50) | 3950 K |
| Resistance tolerance | ±1 % at R25 — not a temperature accuracy figure |
| Probe | Stainless steel, Ø6 × 50 mm, closed tip |
| Probe filling | Epoxy resin |
| Cable | Black PVC, 2-core, 24 AWG |
| Cable length | 3 m |
| Cable routing environment | ≤80 °C — keep the lead clear of flues, flow pipes and hot surfaces |
| Termination | 30 mm stripped tail, 3 mm tinned wire ends |
| Wiring | 2-wire, no polarity |
| Output signal | Passive NTC resistance |
| Installation | Inserted into a dry sensor pocket (closed thermowell) in the tank wall — no contact with stored water, no drain-down |
| Compatible input | Gas boiler controller / DHW thermostat with NTC 10K B3950 sensor input |
| Function | Stored-water temperature feedback only — heat calls, setpoints, limits and protection are performed by the connected controller |
Values describe the standard configuration shown on the specification sheet. Final specifications are subject to technical confirmation. Operating temperature range, ingress rating, resistance curve, pocket dimensions, cable length and termination are confirmed against each order before production — we do not publish figures that are not on the supplied specification.
We build this probe for boiler OEMs, cylinder manufacturers, heating distributors and service companies. Five inputs define the build — send them at enquiry stage and we will confirm the configuration before sampling.
Trial orders welcome. Send the pocket bore and depth, the boiler model (or its NTC curve) and the cable length you need. We will confirm the curve match and build samples before a production run.
Do I have to drain the tank to replace this sensor?
No — that is the point of the dry sensor pocket. The probe sits inside a closed metal well welded into the tank, so the water path and the pressure boundary stay sealed. Pull the old probe out, check the pocket and slide the new one fully in. No isolation, no drain-down, no new gasket.
What does ±1 % actually mean?
It is the resistance tolerance at 25 °C (R25) — the part-to-part spread of the thermistor. It is not ±1 % of reading across the range and not ±1 °C temperature accuracy. Final system accuracy depends on the controller, the beta curve match, the pocket fit and calibration, as the specification sheet itself states.
Will it work with my boiler controller?
Yes, if the sensor input is configured for NTC 10K B3950. Check for "10 kΩ @ 25 °C" and beta 3950 K in the boiler specification or installer menu. If it uses B3977, B3435, 100K or a PT1000 input, send us the model and we will build a matching version.
Does the probe need to be inserted all the way?
Yes. A probe that stops short of the bottom of the well sits in cooler air and reads low, with a slow response. Check the pocket depth against the 50 mm probe, make sure the well is clean, dry and free of scale, and secure the lead so the probe cannot work loose.
Can the cable be run near the flue or the boiler flow pipe?
No. The published ≤80 °C figure is the cable routing environment, not the tank water temperature. PVC hardens and cracks when dressed against a hot surface, and the lead resistance can drift. Route the 3 m cable through cool air and clip it clear of hot pipework; ask us about a high-temperature lead variant if the run cannot avoid heat.
Does this sensor provide overheat or scald protection?
No. It is a passive NTC element that provides temperature feedback only. All setpoints, high-limit cut-outs, interlocks and safety responses are performed by the connected boiler controller or a qualified safety device. It is not a safety sensor and should not be specified as one.
Why does the reading differ from a thermometer at the tap?
A storage tank stratifies. A probe in the upper dry pocket reads the hot top layer, while the bottom of the tank or a distant draw-off can be 15–25 °C cooler when the boiler is idle. That upper reading is what most boiler controls use to start and stop a heat call; it is not the tank average. Add a second, lower pocket if you need the full profile.
Can I get a different probe length, cable or connector?
Yes. Probe diameter and length to suit your pocket bore and depth, other resistance curves, cable lengths, high-temperature jacketing, and terminations including ferrules, JST / Molex housings or your own connector. Send the pocket drawing and boiler model at enquiry stage.
Send the sensor pocket bore and depth, the boiler model and the cable length. We will confirm the NTC curve and probe fit, quote against your volume and build samples before production.
Have questions? Need a quote? We are ready to help! Fill out the form and a member of our sales team will contact you to discuss your requirements. You can also give us a call at (86)177-9158-1665.
boiler temperature sensor-200~650℃ | CE RoHS REACH ISO9001
View More
-55~125℃ | CE RoHS REACH ISO9001
View More
Rm. 1208, Building B, Huixin IBC, No. 1 Zhang Bayi Road, High-tech Zone, Xi'an, Shaanxi, China
Copyright © Xi'an Gavin Electronic Technology Co., Ltd Site Map