A floor sensor gets one chance. It is buried in screed, covered by tile or timber, and from that moment on nobody can reach it again. Every failure — moisture creeping up the cores, alkaline mortar attacking the shell, a cable crushed during pour — is unfixable without breaking the floor. So this sensor is specified for the day it disappears, not the day it ships.
In one line — a 10 kΩ B3950 NTC floor probe with an epoxy-potted, fully sealed tip, white PVC jacket rated to 105 °C, and tinned bare-wire terminals, for hydronic and electric underfloor heating, thermostat OEMs and retrofit projects.
In underfloor heating the sensor is the only component nobody can service. That makes the failure modes worth spelling out.
This is the classic one. Water enters at the terminal end or through a pinhole at the tip, migrates along the conductor by capillary action, and reaches the NTC bead weeks later. The thermostat starts reading 3–8 °C low, the floor overheats, and the fault looks like a thermostat problem.
Fixed by epoxy potting plus a mechanically sealed tip-to-jacket transitionFresh cement screed sits at pH 12–13 for months. Thin ABS shells go brittle, crack at the seam, and let the alkaline water in — which is exactly when the reading starts to drift.
Fixed by an alkali-resistant shell with a full-length encapsulated bodyOne worker stepping on a cable laid over a pipe, or a wheelbarrow crossing the mat, and the conductor work-hardens. It reads fine on the day of commissioning and fails two winters later.
Fixed by stranded copper cores and a thick-wall PVC jacketTwo 10 kΩ NTCs with different B values read identically at 25 °C and disagree by 1–3 °C at 5 °C or 45 °C. The system "works", the floor is simply never the temperature the display says.
Fixed by supplying the exact B value your thermostat expects — B3950 standardThe most widely matched curve in underfloor heating controls. 10 kΩ at 25 °C, B 3950 K, ±0.5 °C — a direct replacement for the sensor most thermostats were designed around.
IP67 sealed probe with a fully encapsulated body. No air pocket, no seam for alkaline water to find, no path along the cores into the element.
Smooth, flexible and easy to pull through conduit. Rated well above any floor-heating surface temperature, and white so it disappears under light screed and timber.
Pre-stripped, pre-tinned red and blue tails. Tinned copper does not oxidise in a damp wall box, and the colour coding removes the guesswork at the thermostat terminals.
Small thermal mass gives a τ of roughly 10 s in still water — quick enough for floor-limit protection without the reading twitching on every burner cycle.
1.5 m to 20 m cable, alternative B values and resistance ratings, connector options and your own labelling — built for thermostat brands and distributors.
Encapsulated NTC bead in a rounded shell, roughly Ø6 mm, with a smooth nose so it slides into a conduit or sits between pipes without snagging. Fast thermal coupling to the screed, no exposed metal to corrode.
Thick-wall white PVC over stranded copper. Flexible down to -30 °C for cold-store and unheated-site installation, rated to 105 °C conductor temperature, and smooth enough to pull through 16 mm conduit.
Red and blue pre-tinned tails, 10 mm stripped. Tinning stops the copper blackening in a damp wall box and gives a clean clamp under a screw terminal — no ferrule needed on most thermostats.
Epoxy fill plus a moulded transition between shell and jacket. The seal is mechanical and chemical, not a bead of silicone — which is the difference between IP67 that holds for a season and one that holds for a decade.
Fix the probe between two heating loops, at least 300 mm from the manifold and away from a pipe joint, then let the screed cover it. Where a conduit is used, cap the end and leave the probe free inside it so it can be replaced.
Land the red and blue tails on the NTC / floor-sensor terminals (usually T1 and T2). NTC elements have no polarity, so either way round reads the same — but keep the pair on one terminal block, not split across two.
Set the floor-limit to the screed manufacturer's figure — typically 45–55 °C surface, lower for timber. Read the floor temperature before the first heat-up and compare it with a contact thermometer; a mismatch means the B value is wrong.
| Sensor type | NTC thermistor, 10 kΩ at 25 °C |
| Beta value (B25/50) | 3950 K standard; 3435 K, 3977 K or customer-specified on request |
| Accuracy | ±0.5 °C at 25 °C (±1 %); ±1.0 °C across 0–60 °C |
| Operating range | -30 to +105 °C (cable and probe) |
| Probe | Encapsulated NTC in rounded shell, ≈Ø6 × 30 mm |
| Probe sealing | Epoxy potted, moulded shell-to-jacket transition, IP67 |
| Cable | White PVC, 2 × 0.22 mm² stranded copper, Ø4.0 mm |
| Cable length | 1.5 m standard; 3 / 5 / 10 / 15 / 20 m to order |
| Terminals | Bare wire, 10 mm stripped and tinned; red / blue colour coded |
| Response time | τ0.9 ≈ 10 s in stirred water |
| Insulation resistance | ≥ 100 MΩ at 500 VDC |
| Dielectric strength | 1500 VAC / 1 min, no breakdown |
| Chemical resistance | Alkali-resistant shell, suitable for direct contact with cement screed |
| Compliance | RoHS / REACH; optional calibration report per batch |
Values describe the standard configuration. Resistance value, B value, cable length and connector are confirmed against each order before production.
Most underfloor heating thermostats are built around a 10 kΩ NTC with a 3950 K beta. But "10 kΩ" alone is not a specification: the resistance curve is defined by the B value, and mismatched curves produce a floor that is quietly 2–3 °C off.
| Curve | R at 25 °C | Beta | Typical use |
|---|---|---|---|
| NTC 10K B3950 | 10 kΩ | 3950 K | Mainstream underfloor heating thermostats (this sensor) |
| NTC 10K B3435 | 10 kΩ | 3435 K | Some European thermostat brands |
| NTC 10K B3977 | 10 kΩ | 3977 K | HVAC and boiler controls |
| NTC 12K / 15K / 100K | 12 / 15 / 100 kΩ | varies | Brand-specific controllers — we build these too |
| PT1000 RTD | 1000 Ω | — | Commercial and building-management systems |
Why this matters more on a floor than anywhere else. A 2 °C error in a room sensor is a comfort complaint. A 2 °C error in a floor sensor is either an overheated screed or a heating system that never reaches setpoint — and you find out only after the floor covering is down.
Floor-limit sensing in screed or between pipe loops, wired to a manifold-zone thermostat. Keeps surface temperature inside the range the floor covering allows.
Laid between heating cable runs and covered by levelling compound. The sealed tip matters here: electric mats run hotter and drive moisture migration faster than a wet system.
Supplied to thermostat brands as the sensor in the box — matched curve, matched cable length, your label on the bag and your connector on the end.
Pulled through existing conduit to replace a failed sensor without lifting the floor — the reason the probe diameter and jacket smoothness are specified as tightly as they are.
Cable length is set by the distance the cable actually travels — out of the screed, up the wall, across to the thermostat — not by floor area. Measure the route, add 1 m, then pick the next standard length up.
| Route length (probe to thermostat) | Order this length | Typical case |
|---|---|---|
| Up to 3 m | 3 m | Bathroom or single-zone retrofit |
| 3–5 m | 5 m | Apartment, thermostat on the same wall |
| 5–10 m | 10 m | Living area, thermostat across the room |
| 10–15 m | 15 m | Multi-zone floor, riser to the next level |
| 15–20 m | 20 m | Villa, long riser, plant-room thermostat |
Never leave the surplus coiled in the screed — coil it in the wall box or at the thermostat. A coil buried in concrete reads its own hot spot, not the floor.
We supply this sensor to heating-control brands, distributors and underfloor heating contractors, so the variable parts are the ones you actually specify.
Trial orders welcome. Send the thermostat model or the curve you need, and we will confirm the matching B value and quote against your volume — samples before production.
Will this sensor work with my underfloor heating thermostat?
It will if your thermostat specifies a 10 kΩ NTC with a 3950 K beta — the most common floor-sensor curve. Send us the thermostat model and we will confirm the match; if it needs a different B value or resistance, we build that too.
Can it be buried directly in cement screed?
Yes. The shell is alkali-resistant and the body is fully encapsulated, so direct contact with fresh screed is fine. Where local practice calls for a conduit, run the probe inside it with a capped end so the sensor stays replaceable.
Is the probe really waterproof, or just splash-proof?
IP67 with an epoxy-potted body and a moulded shell-to-jacket seal — it is designed for permanent burial in damp screed, not just occasional splashes. The bare terminals at the far end must still be made off inside a dry wall box.
Does it matter which wire goes where?
No. An NTC is a pure resistance, so red and blue can be landed either way round on T1 / T2. What does matter is keeping both on the same terminal pair and not sharing the block with mains wiring.
How accurate is it at floor temperatures?
±0.5 °C at 25 °C, and within about ±1.0 °C across 0–60 °C for a standard B3950 curve. Selected ±0.2 °C batches are available if you are calibrating against a reference thermometer at commissioning.
What is the maximum temperature it can take?
105 °C at the cable and probe — far above any underfloor surface limit, which is normally capped at 45–55 °C. The headroom is there because screed during curing and near-manifold positions can run hotter than the design surface temperature.
Can I get a longer cable or a connector on the end?
Yes. Cable runs to 20 m as standard, longer on request, and we can terminate with ferrules, JST or Molex housings, or your own connector and pinout.
Send the thermostat model or the NTC curve you need. We will confirm the B value, quote against your volume and build samples before production.
Have questions? Need a quote? We are ready to help! Fill out the form and a member of our sales team will contact you to discuss your requirements. You can also give us a call at (86)177-9158-1665.
Floor heating temperature sensor-200~650℃ | CE RoHS REACH ISO9001
View More
-55~125℃ | CE RoHS REACH ISO9001
View More
Rm. 1208, Building B, Huixin IBC, No. 1 Zhang Bayi Road, High-tech Zone, Xi'an, Shaanxi, China
Copyright © Xi'an Gavin Electronic Technology Co., Ltd Site Map